mirror of
https://github.com/mukul975/Anthropic-Cybersecurity-Skills.git
synced 2026-07-20 06:20:58 +03:00
Initial commit - 611 cybersecurity skills across all subdomains
This commit is contained in:
@@ -0,0 +1,695 @@
|
||||
---
|
||||
name: detecting-attacks-on-scada-systems
|
||||
description: >
|
||||
This skill covers detecting cyber attacks targeting Supervisory Control and Data
|
||||
Acquisition (SCADA) systems including man-in-the-middle attacks on industrial
|
||||
protocols, unauthorized command injection into PLCs, HMI compromise, historian
|
||||
data manipulation, and denial-of-service against control system communications.
|
||||
It leverages OT-specific intrusion detection systems, industrial protocol anomaly
|
||||
detection, and process data analytics to identify attacks that traditional IT
|
||||
security tools miss.
|
||||
domain: cybersecurity
|
||||
subdomain: ot-ics-security
|
||||
tags: [ot-security, ics, scada, industrial-control, iec62443, intrusion-detection, threat-detection]
|
||||
version: 1.0.0
|
||||
author: mahipal
|
||||
license: MIT
|
||||
---
|
||||
|
||||
# Detecting Attacks on SCADA Systems
|
||||
|
||||
## When to Use
|
||||
|
||||
- When deploying intrusion detection capabilities in a SCADA environment for the first time
|
||||
- When investigating suspected cyber attacks against industrial control systems
|
||||
- When building detection rules for OT-specific attack patterns (Stuxnet, TRITON, Industroyer)
|
||||
- When integrating OT network monitoring with an enterprise SOC for unified threat visibility
|
||||
- When responding to alerts from OT security monitoring tools (Dragos, Nozomi, Claroty)
|
||||
|
||||
**Do not use** for detecting attacks on IT-only networks without SCADA/ICS components, for building generic network IDS rules (see building-detection-rules-with-sigma), or for incident response procedures after an attack is confirmed (see performing-ot-incident-response).
|
||||
|
||||
## Prerequisites
|
||||
|
||||
- Passive network monitoring sensors deployed on SPAN/TAP ports at OT network boundaries
|
||||
- OT intrusion detection system (Dragos Platform, Nozomi Guardian, Claroty xDome, or Suricata with OT rulesets)
|
||||
- Understanding of industrial protocols in use (Modbus, DNP3, OPC UA, EtherNet/IP, S7comm)
|
||||
- Baseline of normal SCADA communication patterns (polling intervals, function codes, register ranges)
|
||||
- Access to process historian data for physical process anomaly correlation
|
||||
|
||||
## Workflow
|
||||
|
||||
### Step 1: Establish SCADA Communication Baselines
|
||||
|
||||
Before detecting anomalies, establish what normal SCADA traffic looks like. Industrial protocols are highly deterministic - the same master polls the same slaves at the same intervals reading the same registers.
|
||||
|
||||
```python
|
||||
#!/usr/bin/env python3
|
||||
"""SCADA Communication Baseline Builder.
|
||||
|
||||
Analyzes OT network traffic to establish deterministic baselines for
|
||||
Modbus/TCP, DNP3, EtherNet/IP, and S7comm communications.
|
||||
"""
|
||||
|
||||
import json
|
||||
import sys
|
||||
from collections import defaultdict
|
||||
from datetime import datetime
|
||||
from statistics import mean, stdev
|
||||
|
||||
try:
|
||||
from scapy.all import rdpcap, IP, TCP, UDP
|
||||
except ImportError:
|
||||
print("Install scapy: pip install scapy")
|
||||
sys.exit(1)
|
||||
|
||||
MODBUS_FUNC_NAMES = {
|
||||
1: "Read Coils", 2: "Read Discrete Inputs",
|
||||
3: "Read Holding Registers", 4: "Read Input Registers",
|
||||
5: "Write Single Coil", 6: "Write Single Register",
|
||||
8: "Diagnostics", 15: "Write Multiple Coils",
|
||||
16: "Write Multiple Registers", 17: "Report Slave ID",
|
||||
22: "Mask Write Register", 23: "Read/Write Multiple Registers",
|
||||
43: "Encapsulated Interface Transport",
|
||||
}
|
||||
|
||||
|
||||
class SCADABaselineBuilder:
|
||||
"""Builds deterministic baselines from SCADA traffic captures."""
|
||||
|
||||
def __init__(self):
|
||||
self.modbus_sessions = defaultdict(lambda: {
|
||||
"func_codes": defaultdict(int),
|
||||
"register_ranges": set(),
|
||||
"intervals": [],
|
||||
"last_seen": None,
|
||||
"request_count": 0,
|
||||
})
|
||||
self.communication_pairs = defaultdict(lambda: {
|
||||
"protocols": set(),
|
||||
"packet_count": 0,
|
||||
"first_seen": None,
|
||||
"last_seen": None,
|
||||
})
|
||||
|
||||
def process_pcap(self, pcap_file):
|
||||
"""Process pcap file to build SCADA baselines."""
|
||||
packets = rdpcap(pcap_file)
|
||||
print(f"[*] Processing {len(packets)} packets for baseline...")
|
||||
|
||||
for pkt in packets:
|
||||
if not pkt.haslayer(IP):
|
||||
continue
|
||||
|
||||
src = pkt[IP].src
|
||||
dst = pkt[IP].dst
|
||||
ts = float(pkt.time)
|
||||
|
||||
# Track communication pairs
|
||||
pair_key = f"{src}->{dst}"
|
||||
pair = self.communication_pairs[pair_key]
|
||||
pair["packet_count"] += 1
|
||||
if pair["first_seen"] is None:
|
||||
pair["first_seen"] = ts
|
||||
pair["last_seen"] = ts
|
||||
|
||||
# Analyze Modbus/TCP
|
||||
if pkt.haslayer(TCP) and pkt[TCP].dport == 502:
|
||||
self._analyze_modbus(pkt, src, dst, ts)
|
||||
|
||||
def _analyze_modbus(self, pkt, src, dst, timestamp):
|
||||
"""Extract Modbus function codes and register ranges."""
|
||||
payload = bytes(pkt[TCP].payload)
|
||||
if len(payload) < 8:
|
||||
return
|
||||
|
||||
# MBAP header: transaction_id(2) + protocol_id(2) + length(2) + unit_id(1) + func_code(1)
|
||||
func_code = payload[7]
|
||||
session_key = f"{src}->{dst}"
|
||||
session = self.modbus_sessions[session_key]
|
||||
|
||||
session["func_codes"][func_code] += 1
|
||||
session["request_count"] += 1
|
||||
session["protocols"] = {"Modbus/TCP"}
|
||||
|
||||
# Track polling intervals
|
||||
if session["last_seen"] is not None:
|
||||
interval = timestamp - session["last_seen"]
|
||||
if 0.01 < interval < 60: # Reasonable polling interval
|
||||
session["intervals"].append(interval)
|
||||
session["last_seen"] = timestamp
|
||||
|
||||
# Extract register range for read/write operations
|
||||
if len(payload) >= 12 and func_code in (1, 2, 3, 4, 5, 6, 15, 16):
|
||||
start_register = (payload[8] << 8) | payload[9]
|
||||
if func_code in (1, 2, 3, 4, 15, 16) and len(payload) >= 12:
|
||||
count = (payload[10] << 8) | payload[11]
|
||||
session["register_ranges"].add((func_code, start_register, start_register + count))
|
||||
|
||||
def generate_baseline(self):
|
||||
"""Generate the baseline profile from collected data."""
|
||||
baseline = {
|
||||
"generated": datetime.now().isoformat(),
|
||||
"modbus_baselines": {},
|
||||
"communication_pairs": {},
|
||||
}
|
||||
|
||||
for session_key, session in self.modbus_sessions.items():
|
||||
avg_interval = mean(session["intervals"]) if session["intervals"] else 0
|
||||
interval_std = stdev(session["intervals"]) if len(session["intervals"]) > 1 else 0
|
||||
|
||||
baseline["modbus_baselines"][session_key] = {
|
||||
"allowed_function_codes": list(session["func_codes"].keys()),
|
||||
"function_code_distribution": {
|
||||
MODBUS_FUNC_NAMES.get(k, f"FC{k}"): v
|
||||
for k, v in session["func_codes"].items()
|
||||
},
|
||||
"polling_interval_avg_sec": round(avg_interval, 3),
|
||||
"polling_interval_stddev": round(interval_std, 3),
|
||||
"register_ranges": [
|
||||
{"func_code": r[0], "start": r[1], "end": r[2]}
|
||||
for r in session["register_ranges"]
|
||||
],
|
||||
"total_requests": session["request_count"],
|
||||
}
|
||||
|
||||
return baseline
|
||||
|
||||
def export_baseline(self, output_file):
|
||||
"""Export baseline to JSON file."""
|
||||
baseline = self.generate_baseline()
|
||||
with open(output_file, "w") as f:
|
||||
json.dump(baseline, f, indent=2)
|
||||
print(f"[*] Baseline saved to: {output_file}")
|
||||
|
||||
# Print summary
|
||||
print(f"\n{'='*60}")
|
||||
print("SCADA COMMUNICATION BASELINE SUMMARY")
|
||||
print(f"{'='*60}")
|
||||
for session, data in baseline["modbus_baselines"].items():
|
||||
print(f"\n Session: {session}")
|
||||
print(f" Function Codes: {data['allowed_function_codes']}")
|
||||
print(f" Polling Interval: {data['polling_interval_avg_sec']}s (+/- {data['polling_interval_stddev']}s)")
|
||||
print(f" Register Ranges: {len(data['register_ranges'])}")
|
||||
print(f" Total Requests: {data['total_requests']}")
|
||||
|
||||
|
||||
if __name__ == "__main__":
|
||||
if len(sys.argv) < 2:
|
||||
print("Usage: python scada_baseline.py <pcap_file> [output.json]")
|
||||
sys.exit(1)
|
||||
|
||||
builder = SCADABaselineBuilder()
|
||||
builder.process_pcap(sys.argv[1])
|
||||
output = sys.argv[2] if len(sys.argv) > 2 else "scada_baseline.json"
|
||||
builder.export_baseline(output)
|
||||
```
|
||||
|
||||
### Step 2: Deploy OT-Specific Detection Rules
|
||||
|
||||
Create detection rules for known SCADA attack patterns including those used by TRITON, Industroyer/CrashOverride, and PIPEDREAM/INCONTROLLER.
|
||||
|
||||
```yaml
|
||||
# Suricata Rules for SCADA Attack Detection
|
||||
# Deploy on IDS sensor monitoring OT network SPAN port
|
||||
|
||||
# --- Modbus Attack Detection ---
|
||||
|
||||
# Unauthorized Modbus write to PLC from non-engineering workstation
|
||||
alert modbus any any -> $OT_PLC_SUBNET 502 (
|
||||
msg:"OT-DETECT Modbus write from unauthorized source";
|
||||
modbus_func:!read_coils; modbus_func:!read_discrete_inputs;
|
||||
modbus_func:!read_holding_registers; modbus_func:!read_input_registers;
|
||||
flow:to_server,established;
|
||||
threshold:type both, track by_src, count 1, seconds 60;
|
||||
classtype:attempted-admin;
|
||||
sid:3000001; rev:1;
|
||||
)
|
||||
|
||||
# Modbus diagnostic/restart command (FC 8) - potential PLC DoS
|
||||
alert modbus any any -> $OT_PLC_SUBNET 502 (
|
||||
msg:"OT-DETECT Modbus diagnostics command to PLC";
|
||||
modbus_func:diagnostics;
|
||||
flow:to_server,established;
|
||||
classtype:attempted-dos;
|
||||
sid:3000002; rev:1;
|
||||
)
|
||||
|
||||
# Modbus broadcast write (unit ID 0) - affects all slaves
|
||||
alert modbus any any -> $OT_PLC_SUBNET 502 (
|
||||
msg:"OT-CRITICAL Modbus broadcast write command";
|
||||
modbus_unit_id:0;
|
||||
flow:to_server,established;
|
||||
classtype:attempted-admin;
|
||||
sid:3000003; rev:1;
|
||||
priority:1;
|
||||
)
|
||||
|
||||
# --- S7comm Attack Detection (Siemens) ---
|
||||
|
||||
# S7comm CPU STOP command - shuts down PLC execution
|
||||
alert tcp any any -> $SIEMENS_PLC_SUBNET 102 (
|
||||
msg:"OT-CRITICAL S7comm CPU STOP command detected";
|
||||
content:"|03 00|"; offset:0; depth:2;
|
||||
content:"|29|"; offset:17; depth:1;
|
||||
flow:to_server,established;
|
||||
classtype:attempted-dos;
|
||||
sid:3000010; rev:1;
|
||||
priority:1;
|
||||
)
|
||||
|
||||
# S7comm PLC program upload (potential logic modification)
|
||||
alert tcp any any -> $SIEMENS_PLC_SUBNET 102 (
|
||||
msg:"OT-CRITICAL S7comm program download to PLC";
|
||||
content:"|03 00|"; offset:0; depth:2;
|
||||
content:"|1a|"; offset:17; depth:1;
|
||||
flow:to_server,established;
|
||||
classtype:attempted-admin;
|
||||
sid:3000011; rev:1;
|
||||
priority:1;
|
||||
)
|
||||
|
||||
# --- DNP3 Attack Detection ---
|
||||
|
||||
# DNP3 cold restart command
|
||||
alert tcp any any -> $OT_RTU_SUBNET 20000 (
|
||||
msg:"OT-CRITICAL DNP3 cold restart command";
|
||||
content:"|05 64|"; offset:0; depth:2;
|
||||
content:"|0d|"; offset:12; depth:1;
|
||||
flow:to_server,established;
|
||||
classtype:attempted-dos;
|
||||
sid:3000020; rev:1;
|
||||
priority:1;
|
||||
)
|
||||
|
||||
# DNP3 firmware update command - potential PIPEDREAM indicator
|
||||
alert tcp any any -> $OT_RTU_SUBNET 20000 (
|
||||
msg:"OT-CRITICAL DNP3 file transfer / firmware update";
|
||||
content:"|05 64|"; offset:0; depth:2;
|
||||
content:"|19|"; offset:12; depth:1;
|
||||
flow:to_server,established;
|
||||
classtype:attempted-admin;
|
||||
sid:3000021; rev:1;
|
||||
priority:1;
|
||||
)
|
||||
|
||||
# --- Network Anomaly Detection ---
|
||||
|
||||
# New device communicating with PLCs (not in baseline)
|
||||
alert ip !$AUTHORIZED_OT_HOSTS any -> $OT_PLC_SUBNET any (
|
||||
msg:"OT-DETECT Unauthorized device communicating with PLC subnet";
|
||||
flow:to_server;
|
||||
threshold:type limit, track by_src, count 1, seconds 3600;
|
||||
classtype:network-scan;
|
||||
sid:3000030; rev:1;
|
||||
)
|
||||
|
||||
# Port scan targeting OT protocols
|
||||
alert tcp any any -> $OT_NETWORK any (
|
||||
msg:"OT-DETECT Port scan targeting industrial protocols";
|
||||
flags:S;
|
||||
threshold:type threshold, track by_src, count 10, seconds 60;
|
||||
classtype:network-scan;
|
||||
sid:3000031; rev:1;
|
||||
)
|
||||
```
|
||||
|
||||
### Step 3: Implement Process Data Anomaly Detection
|
||||
|
||||
Monitor physical process data from the historian to detect attacks that manipulate the process while hiding their effects from operators (the Stuxnet attack pattern).
|
||||
|
||||
```python
|
||||
#!/usr/bin/env python3
|
||||
"""SCADA Process Data Anomaly Detector.
|
||||
|
||||
Monitors historian data to detect physical process anomalies
|
||||
that may indicate cyber attacks manipulating control logic
|
||||
while spoofing sensor readings (Stuxnet-style attacks).
|
||||
"""
|
||||
|
||||
import json
|
||||
import sys
|
||||
import time
|
||||
from collections import deque
|
||||
from dataclasses import dataclass
|
||||
from datetime import datetime
|
||||
from statistics import mean, stdev
|
||||
from typing import Optional
|
||||
|
||||
try:
|
||||
import requests
|
||||
except ImportError:
|
||||
print("Install requests: pip install requests")
|
||||
sys.exit(1)
|
||||
|
||||
|
||||
@dataclass
|
||||
class ProcessVariable:
|
||||
"""Represents a monitored process variable."""
|
||||
tag_name: str
|
||||
description: str
|
||||
unit: str
|
||||
low_limit: float
|
||||
high_limit: float
|
||||
rate_of_change_limit: float # Maximum change per second
|
||||
engineering_low: float
|
||||
engineering_high: float
|
||||
|
||||
|
||||
@dataclass
|
||||
class Anomaly:
|
||||
"""Represents a detected process anomaly."""
|
||||
timestamp: str
|
||||
tag_name: str
|
||||
anomaly_type: str
|
||||
severity: str
|
||||
current_value: float
|
||||
expected_range: str
|
||||
description: str
|
||||
attack_pattern: str = ""
|
||||
|
||||
|
||||
class ProcessAnomalyDetector:
|
||||
"""Detects anomalies in SCADA process data from historian."""
|
||||
|
||||
def __init__(self, historian_url, api_key=None):
|
||||
self.historian_url = historian_url
|
||||
self.api_key = api_key
|
||||
self.variables = {}
|
||||
self.history = defaultdict(lambda: deque(maxlen=1000))
|
||||
self.anomalies = []
|
||||
|
||||
def add_variable(self, var: ProcessVariable):
|
||||
"""Register a process variable to monitor."""
|
||||
self.variables[var.tag_name] = var
|
||||
|
||||
def fetch_current_values(self):
|
||||
"""Fetch current values from historian API."""
|
||||
headers = {}
|
||||
if self.api_key:
|
||||
headers["Authorization"] = f"Bearer {self.api_key}"
|
||||
|
||||
tag_list = list(self.variables.keys())
|
||||
params = {"tags": ",".join(tag_list), "count": 1}
|
||||
|
||||
try:
|
||||
resp = requests.get(
|
||||
f"{self.historian_url}/api/v1/streams/values/current",
|
||||
params=params,
|
||||
headers=headers,
|
||||
timeout=10,
|
||||
verify=False, # Many OT historians use self-signed certs
|
||||
)
|
||||
resp.raise_for_status()
|
||||
return resp.json()
|
||||
except requests.RequestException as e:
|
||||
print(f"[ERROR] Historian API error: {e}")
|
||||
return {}
|
||||
|
||||
def check_value(self, tag_name, value, timestamp):
|
||||
"""Check a process variable value against all detection rules."""
|
||||
var = self.variables.get(tag_name)
|
||||
if not var:
|
||||
return
|
||||
|
||||
self.history[tag_name].append((timestamp, value))
|
||||
|
||||
# Rule 1: Value out of engineering limits
|
||||
if value < var.engineering_low or value > var.engineering_high:
|
||||
self.anomalies.append(Anomaly(
|
||||
timestamp=timestamp,
|
||||
tag_name=tag_name,
|
||||
anomaly_type="OUT_OF_RANGE",
|
||||
severity="critical",
|
||||
current_value=value,
|
||||
expected_range=f"{var.engineering_low}-{var.engineering_high} {var.unit}",
|
||||
description=f"{tag_name} ({var.description}) at {value} {var.unit} - outside engineering limits",
|
||||
attack_pattern="Process manipulation - value driven outside safe operating range",
|
||||
))
|
||||
|
||||
# Rule 2: Rate of change exceeds physical limits
|
||||
history = list(self.history[tag_name])
|
||||
if len(history) >= 2:
|
||||
prev_ts, prev_val = history[-2]
|
||||
try:
|
||||
dt = (datetime.fromisoformat(timestamp) - datetime.fromisoformat(prev_ts)).total_seconds()
|
||||
if dt > 0:
|
||||
rate = abs(value - prev_val) / dt
|
||||
if rate > var.rate_of_change_limit:
|
||||
self.anomalies.append(Anomaly(
|
||||
timestamp=timestamp,
|
||||
tag_name=tag_name,
|
||||
anomaly_type="RATE_OF_CHANGE_VIOLATION",
|
||||
severity="high",
|
||||
current_value=value,
|
||||
expected_range=f"Max rate: {var.rate_of_change_limit} {var.unit}/s",
|
||||
description=(
|
||||
f"{tag_name} changing at {rate:.2f} {var.unit}/s "
|
||||
f"(limit: {var.rate_of_change_limit} {var.unit}/s)"
|
||||
),
|
||||
attack_pattern="Possible sensor spoofing or actuator manipulation",
|
||||
))
|
||||
except (ValueError, TypeError):
|
||||
pass
|
||||
|
||||
# Rule 3: Flatline detection (sensor reading not changing when process is active)
|
||||
if len(history) >= 20:
|
||||
recent_values = [v for _, v in list(history)[-20:]]
|
||||
if len(set(recent_values)) == 1:
|
||||
self.anomalies.append(Anomaly(
|
||||
timestamp=timestamp,
|
||||
tag_name=tag_name,
|
||||
anomaly_type="FLATLINE_DETECTED",
|
||||
severity="high",
|
||||
current_value=value,
|
||||
expected_range="Expected variation during active process",
|
||||
description=f"{tag_name} flatlined at {value} for 20+ consecutive readings",
|
||||
attack_pattern="Stuxnet-style replay attack - frozen sensor value while process is manipulated",
|
||||
))
|
||||
|
||||
# Rule 4: Statistical anomaly (z-score based)
|
||||
if len(history) >= 50:
|
||||
values = [v for _, v in list(history)[-50:]]
|
||||
avg = mean(values)
|
||||
std = stdev(values) if len(values) > 1 else 0
|
||||
if std > 0:
|
||||
z_score = abs(value - avg) / std
|
||||
if z_score > 3.5:
|
||||
self.anomalies.append(Anomaly(
|
||||
timestamp=timestamp,
|
||||
tag_name=tag_name,
|
||||
anomaly_type="STATISTICAL_ANOMALY",
|
||||
severity="medium",
|
||||
current_value=value,
|
||||
expected_range=f"Mean: {avg:.2f}, StdDev: {std:.2f} (z={z_score:.1f})",
|
||||
description=f"{tag_name} value {value} is {z_score:.1f} standard deviations from mean",
|
||||
attack_pattern="Possible gradual process manipulation",
|
||||
))
|
||||
|
||||
def report_anomalies(self):
|
||||
"""Print detected anomalies."""
|
||||
if not self.anomalies:
|
||||
print("[*] No anomalies detected")
|
||||
return
|
||||
|
||||
print(f"\n{'='*70}")
|
||||
print(f"PROCESS ANOMALY DETECTION REPORT - {len(self.anomalies)} anomalies")
|
||||
print(f"{'='*70}")
|
||||
|
||||
for a in self.anomalies:
|
||||
print(f"\n [{a.severity.upper()}] {a.anomaly_type}")
|
||||
print(f" Time: {a.timestamp}")
|
||||
print(f" Tag: {a.tag_name}")
|
||||
print(f" Value: {a.current_value}")
|
||||
print(f" Expected: {a.expected_range}")
|
||||
print(f" Detail: {a.description}")
|
||||
if a.attack_pattern:
|
||||
print(f" Attack Pattern: {a.attack_pattern}")
|
||||
|
||||
|
||||
if __name__ == "__main__":
|
||||
from collections import defaultdict
|
||||
|
||||
detector = ProcessAnomalyDetector(
|
||||
historian_url="https://10.30.1.50:5450",
|
||||
)
|
||||
|
||||
# Define monitored process variables for a chemical reactor
|
||||
detector.add_variable(ProcessVariable(
|
||||
tag_name="REACTOR_01.TEMP",
|
||||
description="Reactor 1 Temperature",
|
||||
unit="C",
|
||||
low_limit=150, high_limit=280,
|
||||
rate_of_change_limit=5.0,
|
||||
engineering_low=100, engineering_high=350,
|
||||
))
|
||||
detector.add_variable(ProcessVariable(
|
||||
tag_name="REACTOR_01.PRESSURE",
|
||||
description="Reactor 1 Pressure",
|
||||
unit="bar",
|
||||
low_limit=2.0, high_limit=8.0,
|
||||
rate_of_change_limit=0.5,
|
||||
engineering_low=0, engineering_high=12.0,
|
||||
))
|
||||
detector.add_variable(ProcessVariable(
|
||||
tag_name="PUMP_03.FLOW",
|
||||
description="Feed Pump 3 Flow Rate",
|
||||
unit="m3/h",
|
||||
low_limit=5.0, high_limit=25.0,
|
||||
rate_of_change_limit=2.0,
|
||||
engineering_low=0, engineering_high=30.0,
|
||||
))
|
||||
|
||||
print("[*] Starting process anomaly monitoring...")
|
||||
print("[*] Press Ctrl+C to stop and generate report")
|
||||
|
||||
try:
|
||||
while True:
|
||||
data = detector.fetch_current_values()
|
||||
for item in data.get("items", []):
|
||||
detector.check_value(
|
||||
item.get("tag"),
|
||||
item.get("value"),
|
||||
item.get("timestamp", datetime.now().isoformat()),
|
||||
)
|
||||
time.sleep(5)
|
||||
except KeyboardInterrupt:
|
||||
detector.report_anomalies()
|
||||
```
|
||||
|
||||
### Step 4: Detect Known ICS Malware Indicators
|
||||
|
||||
Monitor for indicators of compromise (IOCs) associated with known ICS-targeting malware families.
|
||||
|
||||
```yaml
|
||||
# Known ICS Malware Detection Signatures
|
||||
# Reference: MITRE ATT&CK for ICS, CISA ICS-CERT advisories
|
||||
|
||||
malware_families:
|
||||
TRITON_TRISIS:
|
||||
description: "Targets Schneider Electric Triconex Safety Instrumented Systems"
|
||||
target: "Safety controllers (SIS)"
|
||||
network_indicators:
|
||||
- protocol: "TriStation"
|
||||
port: 1502
|
||||
pattern: "Unusual TriStation commands from non-engineering workstation"
|
||||
- protocol: "TCP"
|
||||
pattern: "Connection to Triconex controller from unauthorized IP"
|
||||
host_indicators:
|
||||
- "trilog.exe present on engineering workstation"
|
||||
- "inject.bin in System32 directory"
|
||||
- "imain.bin payload targeting Triconex firmware"
|
||||
detection_rule: |
|
||||
alert tcp !$SIS_ENGINEERING_WS any -> $SIS_CONTROLLERS 1502 (
|
||||
msg:"OT-CRITICAL Unauthorized TriStation connection to SIS";
|
||||
flow:to_server; sid:3000100; rev:1; priority:1;)
|
||||
|
||||
INDUSTROYER_CRASHOVERRIDE:
|
||||
description: "Targets power grid SCADA via IEC 60870-5-101/104, IEC 61850, OPC DA"
|
||||
target: "Power grid substations and SCADA"
|
||||
network_indicators:
|
||||
- protocol: "IEC 60870-5-104"
|
||||
port: 2404
|
||||
pattern: "Rapid sequence of control commands outside normal polling"
|
||||
- protocol: "OPC DA"
|
||||
pattern: "Enumeration of OPC servers followed by write commands"
|
||||
host_indicators:
|
||||
- "haslo.exe (backdoor launcher)"
|
||||
- "61850.dll (IEC 61850 attack module)"
|
||||
- "OPC.dll (OPC DA attack module)"
|
||||
- "104.dll (IEC 104 attack module)"
|
||||
detection_rule: |
|
||||
alert tcp any any -> $SUBSTATION_RTU 2404 (
|
||||
msg:"OT-CRITICAL Rapid IEC 104 control commands - Industroyer pattern";
|
||||
flow:to_server,established;
|
||||
threshold:type threshold, track by_src, count 50, seconds 10;
|
||||
sid:3000110; rev:1; priority:1;)
|
||||
|
||||
PIPEDREAM_INCONTROLLER:
|
||||
description: "Modular ICS attack framework targeting Schneider/OMRON PLCs and OPC UA"
|
||||
target: "Multiple PLC vendors (Schneider, OMRON) and OPC UA servers"
|
||||
network_indicators:
|
||||
- protocol: "CODESYS"
|
||||
port: 1217
|
||||
pattern: "CODESYS runtime exploitation attempts"
|
||||
- protocol: "OPC UA"
|
||||
port: 4840
|
||||
pattern: "OPC UA server enumeration and unauthorized method calls"
|
||||
- protocol: "Modbus"
|
||||
port: 502
|
||||
pattern: "Rapid Modbus write commands to multiple unit IDs"
|
||||
host_indicators:
|
||||
- "TAGRUN tool for OPC UA scanning"
|
||||
- "CODECALL tool for CODESYS exploitation"
|
||||
- "OMSHELL tool for OMRON PLC interaction"
|
||||
detection_rule: |
|
||||
alert tcp any any -> $OT_NETWORK 1217 (
|
||||
msg:"OT-CRITICAL CODESYS runtime connection - PIPEDREAM indicator";
|
||||
flow:to_server,established;
|
||||
sid:3000120; rev:1; priority:1;)
|
||||
```
|
||||
|
||||
## Key Concepts
|
||||
|
||||
| Term | Definition |
|
||||
|------|------------|
|
||||
| SCADA | Supervisory Control and Data Acquisition - architecture for remote monitoring and control of industrial processes via RTUs and communication infrastructure |
|
||||
| IDS/IPS for OT | Intrusion Detection/Prevention Systems designed for industrial protocols, using both signature-based and anomaly-based detection methods |
|
||||
| Process Anomaly | Deviation in physical process behavior (temperature, pressure, flow) that may indicate cyber manipulation of control systems |
|
||||
| Man-in-the-Middle (MITM) | Attack intercepting communication between SCADA master and field devices to modify commands or spoof sensor readings |
|
||||
| Replay Attack | Capturing legitimate SCADA traffic and replaying it to mask malicious changes to the process (used by Stuxnet) |
|
||||
| Protocol Anomaly | Deviation from expected industrial protocol behavior including unauthorized function codes, unusual polling patterns, or command sequences |
|
||||
|
||||
## Tools & Systems
|
||||
|
||||
- **Dragos Platform**: OT cybersecurity platform with threat detection powered by Dragos threat intelligence on ICS-targeting activity groups
|
||||
- **Nozomi Networks Guardian**: OT/IoT visibility and threat detection using asset intelligence, anomaly detection, and vulnerability assessment
|
||||
- **Claroty xDome**: Cyber-physical systems protection with continuous threat monitoring and alert prioritization
|
||||
- **Suricata with ET Open ICS rules**: Open-source IDS/IPS with community-maintained rules for industrial protocol detection
|
||||
- **Zeek (Bro) with OT scripts**: Network security monitor with protocol analyzers for Modbus, DNP3, and BACnet
|
||||
|
||||
## Common Scenarios
|
||||
|
||||
### Scenario: Detecting TRITON-Style Attack on Safety Systems
|
||||
|
||||
**Context**: An OT security monitoring system alerts on unusual TriStation protocol traffic to a Triconex safety controller from an IP address that is not the authorized SIS engineering workstation.
|
||||
|
||||
**Approach**:
|
||||
1. Immediately verify the source IP of the TriStation traffic - is it the authorized SIS engineering workstation or a compromised host?
|
||||
2. Check if there is an authorized maintenance activity scheduled for the SIS controllers
|
||||
3. Capture full packet payload of the TriStation communication for forensic analysis
|
||||
4. Alert the process safety team - SIS compromise is a safety-critical event
|
||||
5. If unauthorized, isolate the source host from the network immediately
|
||||
6. Verify SIS controller logic integrity by comparing running logic against known-good backup
|
||||
7. Check all engineering workstations in the facility for TRITON indicators (trilog.exe, inject.bin)
|
||||
|
||||
**Pitfalls**: Never assume SIS traffic anomalies are false positives - TRITON demonstrated that sophisticated attackers specifically target safety systems. Do not restart the SIS controller without first verifying firmware and logic integrity. Avoid alerting only the IT SOC; the process safety team must be immediately engaged for any SIS-related incident.
|
||||
|
||||
## Output Format
|
||||
|
||||
```
|
||||
SCADA Attack Detection Report
|
||||
===============================
|
||||
Detection Time: YYYY-MM-DD HH:MM:SS UTC
|
||||
Detection Source: [IDS/Anomaly Detector/Process Monitor]
|
||||
|
||||
ALERT DETAILS:
|
||||
Alert ID: [unique identifier]
|
||||
Severity: Critical/High/Medium/Low
|
||||
Attack Category: [Protocol Anomaly/Process Manipulation/Unauthorized Access]
|
||||
MITRE ATT&CK for ICS: [Technique ID and name]
|
||||
|
||||
Source: [IP/hostname]
|
||||
Target: [IP/hostname - device type]
|
||||
Protocol: [Modbus/DNP3/S7comm/etc]
|
||||
Detail: [Specific finding description]
|
||||
|
||||
BASELINE COMPARISON:
|
||||
Normal: [Expected behavior]
|
||||
Observed: [Actual behavior that triggered alert]
|
||||
Deviation: [How the observed differs from baseline]
|
||||
|
||||
RECOMMENDED RESPONSE:
|
||||
1. [Immediate containment action]
|
||||
2. [Verification step]
|
||||
3. [Escalation path]
|
||||
```
|
||||
Reference in New Issue