mirror of
https://github.com/mukul975/Anthropic-Cybersecurity-Skills.git
synced 2026-07-29 15:40:58 +03:00
Complete folder anatomy for all 649 cybersecurity skills + update LICENSE to Mahipal
- Add scripts/agent.py and references/api-reference.md to all remaining skills - Update all 648 LICENSE files: copyright now reads 'Mahipal' - Add implementing-security-monitoring-with-datadog (new skill with full anatomy) - All 649 skills now have: SKILL.md, LICENSE, scripts/agent.py, references/api-reference.md
This commit is contained in:
@@ -0,0 +1,55 @@
|
||||
# API Reference: Implementing ICS Firewall with Tofino
|
||||
|
||||
## OT Protocol Ports
|
||||
|
||||
| Protocol | Port | Layer | DPI Support |
|
||||
|----------|------|-------|-------------|
|
||||
| Modbus/TCP | 502 | TCP | Yes |
|
||||
| EtherNet/IP | 44818 | TCP/UDP | Yes |
|
||||
| DNP3 | 20000 | TCP | Yes |
|
||||
| OPC UA | 4840 | TCP | Yes |
|
||||
| S7comm | 102 | TCP | Yes |
|
||||
| BACnet | 47808 | UDP | Yes |
|
||||
| IEC 61850 MMS | 102 | TCP | Yes |
|
||||
|
||||
## Risky Modbus Function Codes
|
||||
|
||||
| Code | Function | Risk |
|
||||
|------|----------|------|
|
||||
| 5 | Write Single Coil | HIGH |
|
||||
| 6 | Write Single Register | HIGH |
|
||||
| 15 | Write Multiple Coils | HIGH |
|
||||
| 16 | Write Multiple Registers | HIGH |
|
||||
| 22 | Mask Write Register | HIGH |
|
||||
|
||||
## Tofino Xenon Configuration
|
||||
|
||||
```xml
|
||||
<TofinoRule>
|
||||
<Action>Allow</Action>
|
||||
<Source>192.168.1.10</Source>
|
||||
<Destination>192.168.1.50</Destination>
|
||||
<Protocol>Modbus</Protocol>
|
||||
<Port>502</Port>
|
||||
<DPI enabled="true">
|
||||
<AllowedFunctions>1,2,3,4</AllowedFunctions>
|
||||
</DPI>
|
||||
<Logging>true</Logging>
|
||||
</TofinoRule>
|
||||
```
|
||||
|
||||
## Rule Audit Checks
|
||||
|
||||
| Check | Severity | Description |
|
||||
|-------|----------|-------------|
|
||||
| Allow-any-any | CRITICAL | Overly permissive rule |
|
||||
| No default deny | CRITICAL | Missing deny-all at end |
|
||||
| No DPI for OT protocol | HIGH | Missing deep packet inspection |
|
||||
| Write functions allowed | HIGH | Modbus write codes permitted |
|
||||
| Allow without logging | MEDIUM | No audit trail |
|
||||
|
||||
### References
|
||||
|
||||
- Belden Tofino: https://www.belden.com/products/industrial-networking/cybersecurity
|
||||
- IEC 62443-3-3: Industrial Automation Security
|
||||
- NIST SP 800-82: Guide to ICS Security
|
||||
Reference in New Issue
Block a user