# API Reference: Implementing ICS Firewall with Tofino ## OT Protocol Ports | Protocol | Port | Layer | DPI Support | |----------|------|-------|-------------| | Modbus/TCP | 502 | TCP | Yes | | EtherNet/IP | 44818 | TCP/UDP | Yes | | DNP3 | 20000 | TCP | Yes | | OPC UA | 4840 | TCP | Yes | | S7comm | 102 | TCP | Yes | | BACnet | 47808 | UDP | Yes | | IEC 61850 MMS | 102 | TCP | Yes | ## Risky Modbus Function Codes | Code | Function | Risk | |------|----------|------| | 5 | Write Single Coil | HIGH | | 6 | Write Single Register | HIGH | | 15 | Write Multiple Coils | HIGH | | 16 | Write Multiple Registers | HIGH | | 22 | Mask Write Register | HIGH | ## Tofino Xenon Configuration ```xml Allow 192.168.1.10 192.168.1.50 Modbus 502 1,2,3,4 true ``` ## Rule Audit Checks | Check | Severity | Description | |-------|----------|-------------| | Allow-any-any | CRITICAL | Overly permissive rule | | No default deny | CRITICAL | Missing deny-all at end | | No DPI for OT protocol | HIGH | Missing deep packet inspection | | Write functions allowed | HIGH | Modbus write codes permitted | | Allow without logging | MEDIUM | No audit trail | ### References - Belden Tofino: https://www.belden.com/products/industrial-networking/cybersecurity - IEC 62443-3-3: Industrial Automation Security - NIST SP 800-82: Guide to ICS Security